| Materials: - Valve
body: |
DZR BRASS |
| |
- Regulating spindle: |
| |
- Internal shutter:
|
| |
- Sealing elements:
|
| |
- Cover: | |
|
| |
| Temperature adjustment
range: |
85÷120°F (29÷49°C) |
| Temperature set: |
must be commissioned on site to achieve
desired temperature |
| Temperature control: |
±3°F (±2°C) |
| |
| Minimum cold inlet
temperature: |
39°F (4°C) |
| Minimum cold inlet
temperature: |
85°F (29°C) |
| Minimum hot inlet
temperature: |
120°F (49°C) |
| Minimum hot inlet
temperature: |
185°F (85°C) |
| Wire Length: |
10.50" |
| |
| Maximum working pressure
(static): |
140 psi (10 bar) |
| Maximum working pressure
(dynamic): |
70 psi (5 bar) |
| Maximum working pressure
(dynamic): |
1.5 psi (0.1 bar) |
| |
| Maximum unbalanced dynamic
supply (hot/cold or cold/hot): |
6:1 |
| |
| Minimum temperature
differential between hot water inlet and mixed
water outlet to ensure thermal shutoff
function: |
18°F (10°C) |
| Minimum temperature
differential between mixed water outlet and cold
water inlet to ensure stable operation: |
9°F (5°C) |
| Minimum flow rate for
stable operation: |
1 gpm (4 l/min) |
| Certified to: |
ASSE 1016 |